Proof wall

The reports

Real floors we coated, tested by a third party. Wet pendulum, after the coating went on. Site details blurred for confidentiality. Tap any report to open it.

Before and after on the same floor

Four Seasons, Sydney NSWLevel 3 spa amenities 35to61mean BPN
Hotel pool surrounds, Brisbane CBDPool surrounds 32to58mean BPN, P2 to P5

What the trade says

Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer Review from a trade customer

Wear

Held P4 at 500, 1,000, 2,000 and 5,000 wear cycles in an accelerated wear test to AS 4586. Sliptest Australia, NATA accreditation 15374, report AWT011021-1.

The fine print

Most of these are in-situ tests to AS 4663, which reports a value and does not pass or fail a floor. Where a report printed no classification, we band its own figure against AS 4586 Table 2.

A slip test measures a floor at a point in time. Wear, damage and the wrong cleaning all move the number, which is why commercial work gets a re-test schedule.